APC Smart-UPS SRT 2200VA 230V - SRT2200RMXLI

Batteries & Runtime

Run Time : View Runtime Graph
Efficiency : View Runtime Graph

Front View :

1. POWER ON/OFF button 2. Load icon Disable/mute audible alarm icon 3. UPS status information
4. Operation mode icons 5. ESCAPE button 6. OK button
7. UP/DOWN buttons 8. Controllable outlet group status icons 9. Battery status icons

Rear View :

1. SmartSlot 2. AC input power cable or hardwire input box 3. External battery power and communication connector
4. Controllable outlet group 1 5. Chassis ground screws 6. Controllable outlet group 2
7. EPO terminal 9. Serial Com 10. USB port
  • Predictive failure notification: Provides early-warning fault analysis ensuring proactive component replacement.
  • User-replaceable batteries: Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
  • Audible alarms: Provides notification of changing utility power and UPS power conditions
  • Automatic self-test: Periodic battery self-test ensures early detection of a battery that needs to be replaced.
  • Disconnected battery notification: Warns when a battery is not available to provide backup power.
Availability
  • Intelligent battery management: Maximizes battery performance, life, and reliability through intelligent, precision charging.
  • Scalable runtime: Allows additional run time to be quickly added as needed.
  • Temperature-compensated battery charging: Prolongs battery life by regulating the charge voltage according to battery temperature.
  • Automatic internal bypass: Supplies utility power to the connected loads in the event of a UPS power overload or fault.
  • Automatic restart of loads after UPS shutdown: Automatically starts up the connected equipment upon the return of utility power.
  • Hot-swappable batteries: Ensures clean, uninterrupted power to protected equipment while batteries are being replaced
Save time with easy and convenient remote/network accessibility.

Network manageable via serial, USB or Ethernet. Includes Powerchute Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.

Avoids costly power problems by keeping your IT equipment and data protected and available.

Network grade power conditioning protects from damaging surges and disruptive noise. The double conversion architecture provides tight voltage regulation, frequency regulation ,and zero transfer time to battery during power events.

Low operating and maintenance costs with proven reliability and intelligent battery management.

Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature compensated charging. Automatic self tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy to connect, hot-swappable battery modules provide battery replacement without powering down.

Peace of mind that comes with full equipment compatibility and reliability of a leader

Provides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.

Main Input Voltage : 230 V
Other Input Voltage : 220 V, 240 V
Main Output Voltage : 230 V
Other Output Voltage : 220 V, 240 V
Rated Power In Watt : 1980 W
Rated Power In Va : 2200 VA
Battery Type : Lead-acid battery
Number Of Battery Filled Slots : 1
Battery Recharge Time : 3 h
Number Of Battery Replacement Quantity : 1
Battery Voltage : 72 V
Battery Charger Power : 122 W rated
Battery Life : 3 to 5 year(s)
Replacement Battery : APCRBC141
Network Frequency : 40 to 70 Hz auto-sensing
Input Voltage Limits : 100 to 275 V adjustable (half load)
Maximum Configurable Power In Va : 2200 VA
Maximum Configurable Power In Watt : 1980 W
Output Frequency : 50/60 Hz +/- 3 Hz sync to mains
Wave Type : Sine wave
Ambient Air Temperature For Operation : 0 to 40°C
Relative Humidity : 0 to 95% non-condensing
Operating Altitude : 0 to 10000 ft
Ambient Air Temperature For Storage : -20 to 50°C
Storage Relative Humidity : 0 to 95% non-condensing
Storage Altitude : 0.00 to 15240.00 m
Acoustic Level : 55 dBA
Dimension (H x W x D) : 8.5 x 43.2 x 58.4 cm
Net Weight : 25 kg
Warranty : 3 years repair or replace (excluding battery) and 2 years for battery